Product Specifications
| Reference Point |
Temp °C |
0 |
Res ohm |
1000,00 |
| Temp °C |
R nom Ohm |
R min Ohm |
R max Ohm |
| -40 |
842,7 |
834,3 |
851,1 |
| -25 |
900,1 |
891,2 |
909,2 |
| 0 |
1000,0 |
990,0 |
1010,0 |
| 25 |
1097,3 |
1086,3 |
1108,3 |
| 50 |
1194,0 |
1182,1 |
1205,9 |
| 75 |
1289,9 |
1277,0 |
1302,8 |
| 100 |
1385,1 |
1371,2 |
1398,9 |
| 125 |
1479,5 |
1464,3 |
1493,9 |
| 150 |
1573,3 |
1557,6 |
1589,0 |
| 175 |
1666,3 |
1649,6 |
1682,9 |
| 200 |
1758,6 |
1741,0 |
1776,2 |
| 225 |
1850,1 |
1831,6 |
1568,6 |
| 250 |
1941,0 |
1921,6 |
1960,4 |
Electrical Specification
| Sensor |
PT 1000 |
| Resistance at 0°C |
1000,0 ohms +- 1% |
| Insulation strength |
|
| |
test voltage |
500 V (eff) |
| |
wave form |
sinus |
| |
time |
1 min |
| |
I (eff) <= |
1 mA |
| |
|
|
| Operating temperature range |
- 40° to + 250° C |
| Overheat temperature for 5 min |
300° C |
| Thermoschock |
from 150° C to 0° C |
| Error Rate |
>100ppm |
| Test on Climachange |
EN 144000 |
Applications: Air Condition, Heating Systems, White Goods etc...
Customization and engineering alterations possible at any time
| |